Heating Requirements
Input BTU/Hr =   Blower SCFM * Temp Rise * Density Factor

.83


Temp Rise =   Input BTU/Hr * .83

CFM * Density Factor


Density Factor =   1.08 +  (70-Blower Temp) * .024

10



Output BTU/Hr
Output BTU/Hr =   Input BTU/Hr * .83
Ventilation Direct is committed to customer service and on time, accurate delivery of superior Ventilation products.

Call 1.866.433.8335 for a friendly customer service representative that can customize your exhaust fan, heater or supply air package while providing you a fast quotation including drawings and submittal packages. Our product line includes UL and ANSI listed commercial and industrial exhaust fans, heaters, make-up air units, motors and more with a two year warranty.